Mikhail ChusavitinandClaude Sonnet 5 7ed652c5b1 feat: autotune PSU capacity from the same full-load run as fan ceilings
Extract the fan peak-tracking into observedPeakStore (observe max under
load, hold >= minHold to reject spikes, round, persist JSON) and add a
second instance for PSU draw (psu-observation.json, keyed by PSU
ordinal). Fed from samplePSUPower like fans are from sampleFanSpeeds, so
any full-load run refines it — the Fan Ceiling Check (which also samples
PSU power at a slow cadence off its loop and writes psu_<i>_peak_w), a
burn, thermal cycling, and the 5s web metrics collector.

/topo PSU cards now scale the load fill by wattage_w when the BMC
reports it, else by the observed peak draw — marked "~N% load". This
MSI stand's BMC gives only instantaneous input power, so the observed
peak is the only capacity figure available.

Fan behaviour is unchanged (tests exercise updateFanObservation /
estimateFanDutyCyclePctFromObservation / ResolveFanMaxRPM through the
new store).

Co-Authored-By: Claude Sonnet 5 <noreply@anthropic.com>
Claude-Session: https://claude.ai/code/session_019VHG21rgTUiR1G3qFHTVmN
2026-09-04 12:53:13 +03:00

108 lines
5.5 KiB
Markdown
Raw Permalink Blame History

This file contains ambiguous Unicode characters
This file contains Unicode characters that might be confused with other characters. If you think that this is intentional, you can safely ignore this warning. Use the Escape button to reveal them.
# Decision: Fan check discovers the RPM ceiling by CPU+GPU load, not by forcing fans over the BMC
**Date:** 2026-09-04
**Status:** active
## Context
We want a SAT test that pushes every system fan to its top speed, records that
speed as the fan's ceiling, and flags a fan that will not spin. The recorded
ceiling is what the Topology view sizes each fan tile against
(`platform.ResolveFanMaxRPM`).
The obvious approach — force the fans to 100% PWM over IPMI/Redfish and read the
resulting RPM — does not work on our current platform:
- Stand: MSI G4201 / MS-S3831, AMI MegaRAC BMC (fw 1.08).
- Every documented host-side fan-control OEM command returns
`rsp=0xc1 Invalid command`: Supermicro `0x30 0x45`, ASRock/AMI reference
`0x3a 0x01 / 0xd0 0x12 / 0xd0 0x0f / 0xd6 / 0xd7 / 0xda`, `0x30 0x30..0x32`.
BIOS `KCS Access Control Policy = Allow All`, so this is not KCS filtering —
MSI simply does not implement them.
- The MSI G4201 Redfish API guide documents Thermal as **GET only**; no
fan-mode / fan-PWM PATCH endpoint exists.
- The only fan knob in BIOS is `Fan PWM Offset` (0100, additive to the auto
curve, reboot-gated) — not a runtime 100% force.
## Decision
The `fan` SAT test (`platform.RunFanCheck`, formerly the unwired
`RunFanStressTest`) drives load, not the BMC:
1. Start `stressapptest` (CPU + memory) and, when a GPU is present, the
**hottest sustained GPU load**`dcgmproftester -t 1004` /
`targeted_power`, via `resolveBenchmarkPowerLoadCommand`, the same engine
Power/Thermal Fit uses — **simultaneously**, each in its own goroutine.
NOT `bee-gpu-burn`: that is a compute-throughput burn that tops out around
88% of TDP (measured ~525 W of 600 W on RTX PRO 6000 Blackwell) and never
makes the fans demand their true ceiling. A first run on the MSI stand with
`bee-gpu-burn` peaked F2U fans at 24 400 RPM vs a historical 26 000.
A missing GPU is not an error — CPU/memory load alone exercises the cooling
loop. Load sources reach full power at different times, so the plateau clock
only starts once every launched source reports its process running (plus a
fixed GPU ramp grace).
2. Sample every fan on an adaptive interval (floor 1 s). Each read is
time-boxed (`readFansBounded` — a goroutine abandoned on timeout, so a
KCS-wedged `ipmitool` can never block the loop); when reads are slow the
interval backs off geometrically to 30 s and tightens again when they
recover. Under 8-GPU + CPU load on the MSI stand, `ipmitool sdr type Fan`
took ~14 s/call and at one point wedged for minutes — without this the
"1 Hz" sampler silently degraded to one sample per 14 s and the plateau
timer ran on stale data. A plateau is only declared while telemetry is
healthy (interval near the floor, ≥5 recent samples); a degraded run just
rides out to `MaxLoadSec` and records the peak it saw. Per fan, track the
peak RPM and the last time it climbed by more than `PlateauDeltaRPM`
(default 50).
3. When no fan has climbed for `PlateauHoldSec` (default 60 s) and at least one
fan rose meaningfully above baseline, declare the ceiling found and stop —
**success**. `MaxLoadSec` (default 900 s) is a hard cap; hitting it is also
success (the highest RPM seen is still recorded).
4. Persist each peak through `updateFanObservation`
(`/var/log/bee-sat/fan-observation.json`), which is what `ResolveFanMaxRPM`
reads.
## The observed-peak store (autotune primitive)
`platform.observedPeakStore` (`observed_peaks.go`) is the shared mechanism:
observe the max value per key while the box is under load, require a candidate
to hold ≥ `minHold` before it sticks (rejects spikes), round up, persist to a
`{"<jsonKey>": {key: peak}}` JSON file. Two instances:
- `fanPeaks``fan-observation.json` `max_rpm`, keyed by fan name, round-up 1000.
- `psuPeaks``psu-observation.json` `max_w`, keyed by **PSU ordinal**, round-up 50.
Both are fed from the ordinary telemetry paths — `sampleFanSpeeds` and
`samplePSUPower` call `update*Observation` — so **any** full-load run refines
them: the Fan Ceiling Check itself, a burn, thermal cycling, power
calibration, and the 5 s web metrics collector while any of those run. There
is no separate "PSU autotune" test: the fan check's max-CPU+GPU load is
already the right moment to observe peak PSU draw, and it samples PSU power at
a slow cadence off its own loop (`psu_<i>_peak_w` in the summary).
This exists because BMCs like the MSI stand's report only instantaneous PSU
input power, no nameplate rating. `/topo` PSU cards scale the load fill by the
real `wattage_w` when present, otherwise by `ObservedPSUMaxW()` — marked as an
estimate (`~N% load`).
## Verdict mapping
- A fan reading **0 RPM**, or IPMI status **cr/nr**, while under full load →
`FAILED` (dead / stuck rotor).
- No load source available (no `stressapptest`/`stress-ng` and no GPU burn
tool), or no fan sensors at all → `platform.ErrTestNotApplicable`, which the
task layer lands as **cancelled ("not applicable")**, never failed, with a
detailed log. An engineer must not see a red for "this platform can't run the
test".
## Tier
Load only (`/load`, "3. Load"). It is a sustained full-load test, so it does
not belong on the read-only Check page. Added to the stress-mode `Run All`.
## Consequences
- The ceiling is *observed*, not a spec value — only as high as the load drove
the fans. Good enough for tile sizing and stuck-fan detection.
- If a future platform does expose a safe host-side fan force, revisit: a real
100% force is a stronger test than load-driven ramp.